dc.description.abstract

Dissolved gas analysis (DGA) of transformer oil is one of the most effective power transformer condition monitoring tools. There are many interpretation techniques for DGA results however all current techniques rely on personnel experience more than analytical formulation. As a result, the current techniques do not necessarily lead to the same conclusion for the same oil sample. A significant number of DGA results fall outside the proposed codes of the ratio-based interpretation techniques and cannot be diagnosed using these methods. Moreover, ratio methods fail to diagnose multiple fault conditions due to the mixing up of produced gases. To overcome these limitations, this paper introduces a new fuzzy logic approach that aids in standardizing DGA interpretation and identifies transformer critical ranking based on DGA data. The approach relies on incorporating all traditional DGA interpretation techniques (Roger, Doerenburg, IEC, key gas and Duval triangle methods) into one expert model. In this context, DGA results of 338 oil samples of pre-known fault conditions that were collected from different transformers of different rating and different life span are used to establish the model. Traditional DGA interpretation techniques are used first to analyze the DGA results to evaluate the consistency and accuracy of each method in identifying various faults. Results of this analysis were then used to develop the proposed fuzzy logic model. The model is validated using another set of DGA data that were collected form previously published papers.

dc.publisherElsevier Ltd
dc.subjectTransformer diagnosis
dc.subjectFuzzy logic
dc.subjectTransformer failure
dc.subjectDGA
dc.titleA new fuzzy logic approach to identify power transformer criticality using dissolved gas-in-oil analysis
dc.typeJournal Article
dcterms.source.volume67
dcterms.source.startPage401
dcterms.source.endPage408
dcterms.source.issn0142-0615
dcterms.source.titleElectrical Power and Energy Systems
curtin.departmentDepartment of Electrical and Computer Engineering
curtin.accessStatusFulltext not available


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record