    High performance communication redundancy in a digital substation based on IEC 62439-3 with a station bus configuration

    Access Status
    Fulltext not available
    Authors
    Kumar, S.
    Das, N.
    Islam, Syed
    Date
    2015
    Type
    Conference Paper
    
    Metadata
    Show full item record
    Citation
    Kumar, S. and Das, N. and Islam, S. 2015. High performance communication redundancy in a digital substation based on IEC 62439-3 with a station bus configuration, in Proceedings of the Australasian Universities Power Engineering Conference (AUPEC), Sep 27-30 2015. Wollongong, NSW: IEEE.
    Source Title
    2015 Australasian Universities Power Engineering Conference: Challenges for Future Grids, AUPEC 2015
    DOI
    10.1109/AUPEC.2015.7324838
    ISBN
    9781479987252
    School
    Department of Electrical and Computer Engineering
    URI
    http://hdl.handle.net/20.500.11937/26294
    Collection
    • Curtin Research Publications
    Abstract

    High speed communication is critical in a digital substation from protection, control and automation perspectives. Although International Electro-Technical Commission (IEC) 61850 standard has proven to be a reliable guide for the substation automation and communication systems, yet it has few shortcomings in offering redundancies in the protection architecture, which has been addressed better in IEC 62439-3 standard encompassing Parallel Redundancy Protocol (PRP) and High-Availability Seamless Redundancy (HSR). Due to single port failure, data losses and interoperability issues related to multi-vendor equipment, IEC working committee had to look beyond IEC 61850 standard. The enhanced features in a Doubly Attached Node components based on IEC 62439-3 provides redundancy in protection having two active frames circulating data packets in the ring. These frames send out copies in the ring and should one of the frame is lost, the other copy manages to reach the destination node via an alternate path, ensuring flawless data transfer at a significant faster speed using multi-vendor equipment and fault resilient circuits. The PRP and HSR topologies provides higher performance in a digitally protected substation and promise better future over the IEC 61850 standard due to its faster processing capabilities, increased availability and minimum delay in data packet transfer and wireless communication in the network. This paper exhibits the performance of PRP and HSR topologies focusing on the redundancy achievement within the network and at the end nodes of a station bus ring architecture, based on IEC 62439-3.

    Related items

    Showing items related by title, author, creator and subject.

    • Performance evaluation of a process bus architecture in a zone substation based on IEC 61850-9-2
      Kumar, S.; Das, N.; Islam, Syed (2016)
      Ethernet communication has been the back bone of high speed communication in digital substations from protection relaying, control and automation perspective. Major substation manufacturers have been constantly upgrading ...
    • Analysis of end-To-end delay characteristics for various packets in IEC 61850 substation communications system
      Das, N.; Ma, W.; Islam, Syed (2015)
      © 2015 IEEE. Substation plays an important role in power system communications for safe and reliable operation of entire power networks. Substation communication networks are connected with various substation intelligent ...
    • Performance evaluation of two interconnected high voltage utility substations using PRP topology based on IEC 62439-3
      Kumar, S.; Das, Narottam; Islam, Syed (2018)
      © 2017 IEEE. In a modern power system network having multiple interconnected High Voltage (HV) substations, communication amongst Intelligent Electronic Devices (IED) becomes an important feature in an automation system. ...
    Advanced search

    Browse

    Communities & CollectionsIssue DateAuthorTitleSubjectDocument TypeThis CollectionIssue DateAuthorTitleSubjectDocument Type

    My Account

    Admin

    Statistics

    Most Popular ItemsStatistics by CountryMost Popular Authors

    Follow Curtin

    • 
    • 
    • 
    • 
    • 

    CRICOS Provider Code: 00301JABN: 99 143 842 569TEQSA: PRV12158

    Copyright | Disclaimer | Privacy statement | Accessibility

    Curtin would like to pay respect to the Aboriginal and Torres Strait Islander members of our community by acknowledging the traditional owners of the land on which the Perth campus is located, the Whadjuk people of the Nyungar Nation; and on our Kalgoorlie campus, the Wongutha people of the North-Eastern Goldfields.