Harmonics issues of three-phase diode rectifiers with a small DC link capacitor
Access Status
Authors
Date
2014Type
Metadata
Show full item recordCitation
Source Title
ISBN
School
Collection
Abstract
© 2014 IEEE. This paper presents effects of DC link capacitor sizes in a three phase diode rectifier on input current harmonics at a system level. A small DC link capacitor generates a resonant frequency with a line inductor which can affect and increase the input current harmonics. According to IEC 61000-3-2 and IEC 61000-3-12 standards, low order current harmonics of a power electronic system should be controlled below a certain limits but at a power system level, voltage harmonics are important and should be reduced. SABER simulations have been carried out for a three phase motor drive system with different DC link capacitors and at different power levels in order to analyze the input current harmonics and the power quality of the power network.
Related items
Showing items related by title, author, creator and subject.
-
Soltani, H.; Davari, P.; Kumar, D.; Zare, Firuz; Blaabjerg, F. (2017)© 2017 IEEE. Harmonic and interharmonic distortions are considered as the main power quality issues especially in the distribution networks. The double-stage Adjustable Speed Drives (ASDs) in which the front-end diode ...
-
Maticevic, Stjepan (2011)This work has focused on understanding the nature and impact of non-linear loads on isolated industrial power systems. The work was carried out over a period of 8 years on various industrial power systems: off-shore oil ...
-
Davari, P.; Yang, Y.; Zare, Firuz; Blaabjerg, F. (2016)© 1982-2012 IEEE. The majority of the industrial motor drive systems are equipped with the conventional line-commutated front-end rectifiers and being one of the main sources of harmonics in the power line. While a parallel ...