Show simple item record

dc.contributor.authorLiang, R.
dc.contributor.authorYang, Z.
dc.contributor.authorPeng, N.
dc.contributor.authorLiu, C.
dc.contributor.authorZare, Firuz
dc.date.accessioned2018-05-18T07:55:45Z
dc.date.available2018-05-18T07:55:45Z
dc.date.created2018-05-18T00:23:17Z
dc.date.issued2017
dc.identifier.citationLiang, R. and Yang, Z. and Peng, N. and Liu, C. and Zare, F. 2017. Asynchronous fault location in transmission lines considering accurate variation of the ground-mode traveling wave velocity. Energies. 10 (12): Article ID 1957.
dc.identifier.urihttp://hdl.handle.net/20.500.11937/66722
dc.identifier.doi10.3390/en10121957
dc.description.abstract

This paper proposes a grounding fault location method in transmission lines based on time difference of arrival (TDOA) of ground-mode and aerial-mode traveling waves (TWs). The frequency-dependent characteristics of transmission lines cause different frequencies to have different attenuations and phase lags of different frequency components in traveling waves, which leads to the change of TWs velocities with different propagation distances. Due to these different propagation paths, the wave velocity variations of ground-mode should be considered as a main variable while the velocity of aerial-mode can be seen as a constant factor. A quadratic function that can illustrate the tendency of variation of ground-mode wave velocity is proposed by considering the relation between the wave velocity and fault distance. The least squares method is used to solve the quadratic function of different lines. Combining the quadratic formula and the incident TWs of each mode detected at both terminals of the line, a novel fault location method is proposed. First, according to the maximum and minimum ground-mode velocities, a fault scope can be acquired. Then, more accurate fault scopes and ground-mode velocities can be obtained by iteration computation. Finally, an accurate fault position is acquired when the fault scope is sufficiently small. PSCAD/EMTDC software is used to conduct fault simulations in order to verify the feasibility and accuracy of the method.

dc.publisherM D P I AG
dc.rights.urihttp://creativecommons.org/licenses/by/4.0/
dc.titleAsynchronous fault location in transmission lines considering accurate variation of the ground-mode traveling wave velocity
dc.typeJournal Article
dcterms.source.volume10
dcterms.source.number12
dcterms.source.issn1996-1073
dcterms.source.titleEnergies
curtin.departmentSchool of Electrical Engineering, Computing and Mathematical Science (EECMS)
curtin.accessStatusOpen access


Files in this item

Thumbnail

This item appears in the following Collection(s)

Show simple item record

http://creativecommons.org/licenses/by/4.0/
Except where otherwise noted, this item's license is described as http://creativecommons.org/licenses/by/4.0/