Performance evaluation of online transformer internal fault detection based on transient overvoltage signals
Access Status
Authors
Date
2017Type
Metadata
Show full item recordCitation
Source Title
ISSN
School
Collection
Abstract
© 1994-2012 IEEE. Winding deformation is a critical power transformer issue that needs to be detected as soon as it emerges due to its progressive nature and severe consequences it may lead to. Frequency response analysis (FRA) is the only reliable technique currently used to detect such deformation. However, the technique is conducted offline that may cause interruption to the electricity grid when taking an operating transformer out of service for testing. Moreover, as the current FRA technique is only conducted on suspected units, a mechanical fault may emerge and progress before the utility becomes aware of. To overcome these limitations, this paper presents a practical feasibility study to detect transformer winding deformations online. The technique relies on utilizing transient overvoltage signals that a transformer is subjected to during its normal operation as a natural variable frequency excitation source. The feasibility of utilizing various transient overvoltage signals as excitation source for transformer FRA signature measurement is firstly investigated and optimum signal parameters are recommended based on signal voltage and energy spectrum analyses. Secondly, the proposed technique is verified through simulation analysis by comparing the transformer frequency response signatures when transient overvoltage and conventional sweep frequency voltage are used as excitation sources. Also, experimental testing is conducted to assess the feasibility of the proposed technique to identify various winding deformations such as radial buckling, telescoping and short circuit turns. Custom-made capacitive voltage divider is developed to accurately detect the response of transient overvoltage signals generated due to environmental conditions or power system switching operations. The proposed technique along with the developed capacitive voltage divider is implemented on a 3-phase Wye-Delta, 50 Hz, 31.5 MVA, 110/10.5 kV power transformer to measure the frequency response signatures of the high voltage winding.
Related items
Showing items related by title, author, creator and subject.
-
Aljohani, O.; Abu-Siada, Ahmed (2016)Although a frequency response analysis (FRA) technique has been extensively used to detect mechanical deformation within power transformers, interpretation of FRA signature still needs a high level of expertise to identify ...
-
Zhao, X.; Yao, C.; Li, C.; Zhang, C.; Dong, S.; Abu-Siada, Ahmed; Liao, R. (2019)Power transformers are prone to short circuit faults and external harsh environmental conditions that may result in various internal winding and core deformations. Frequency response analysis (FRA) is the current technique ...
-
Hashemnia, Seyednaser; Abu-Siada, Ahmed; Islam, Syed (2015)Frequency response analysis (FRA) has become a widely accepted tool to detect power transformer winding deformation due to the development of FRA test equipment. Because FRA relies on graphical analysis, interpretation ...